Product Model

A1C 125 TMF 40-400 4p F F

In Stock
Last updated: 2025/5/2
ABB A1C 125 TMF 40-400 4p F F

Selling Points

  • 1High Electrical Durability: Withstands 1500 electrical cycles and 8500 mechanical cycles for long-lasting performance.
  • 2Thermomagnetic Release: Ensures reliable operation under various conditions, including short circuits.
  • 3Front Terminal Connection: Convenient and accessible front terminals simplify installation and maintenance.
  • 4Compliance with IEC Standards: Meets international safety standards for electrical equipment, ensuring high reliability and safety.
  • 5Versatile Voltage Range: Operates at 240 V AC, 380 V AC, 415 V AC, and 440 V AC with short-circuit breaking capacities up to 25 kA.
Product Details
A1C 125 TMF 40-400 4p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
1SDL000183R0001 9AKK108467A6707
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
60 mm
Product Net Weight
1 kg
Product Main Type
SACE FORMULA
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Electrical Durability
1500 cycle
Mechanical Durability
Nr. Operations 8500 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Power Loss
at Rated Operating Conditions per Pole 4.5 W
Rated Current (In)
Main Circuit 40 A
Rated Impulse Withstand Voltage (Uimp)
6 kV
Rated Insulation Voltage (Ui)
690 V
Rated Operational Voltage
550 V AC 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 15 kA (380 V AC) 12.5 kA (415 V AC) 6.25 kA (440 V AC) 5 kA (480 V AC) 4 kA (500 V AC) 2.5 kA (250 V DC) 2 Poles in Series 5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 30 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 20 kA (480 V AC) 15 kA (500 V AC) 8 kA (250 V DC) 10 kA
Rated Uninterrupted Current (Iu)
125 A
Release
TMF
Release Type
TM
Short-Circuit Performance Level
C
Standards
IEC
Sub-type
A1
Terminal Connection Type
Front
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA066749R1

Specifications may be subject to change without notice