Product Model
A1N 125 TMF 50-500 1p F F

Selling Points
- 1Breaks short circuits up to 25 kA at 240 V AC and 10 kA at 125 V DC.
- 2Ensures reliable operation with a thermomagnetic release mechanism.
- 3Easy installation with front terminal connections.
- 4Meets EU Directive 2011/65/EU and Amendment 2015/863 for RoHS compliance.
- 5Designed for 1500 electrical cycles and 8500 mechanical cycles.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 1SDL000183R0001 9AKK108467A6707 | Product Net Width | 25.4 mm |
Product Net Height | 130 mm | Product Net Depth / Length | 60 mm |
Product Net Weight | 0.25 kg | Product Main Type | SACE FORMULA |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | F | Electrical Durability | 1500 cycle |
Mechanical Durability | Nr. Operations 8500 cycle | Number of Poles | 1P |
Opening Time | CB with SOR 15 ms CB with UVR 15 ms | Power Loss | at Rated Operating Conditions per Pole 5.5 W |
Rated Current (In) | Main Circuit 50 A | Rated Impulse Withstand Voltage (Uimp) | 6 kV |
Rated Insulation Voltage (Ui) | 690 V | Rated Operational Voltage | 415 V AC 125 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (240 V AC) 12.5 kA (380 V AC) 2.5 kA (415 V AC) 1.25 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (240 V AC) 25 kA (380 V AC) 5 kA (415 V AC) 5 kA (125 V DC) 10 kA |
Rated Uninterrupted Current (Iu) | 125 A | Release | TMF |
Release Type | TM | Short-Circuit Performance Level | N |
Standards | IEC | Sub-type | A1 |
Terminal Connection Type | Front | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
Manufacturer ID | 1SDA066690R1 |
Specifications may be subject to change without notice