Product Model

A2N 250 TMF 175-1750 2p F F

In Stock
Last updated: 2025/4/30
ABB A2N 250 TMF 175-1750 2p F F

Selling Points

  • 1Thermal Magnetic Trip Device: Ensures reliable and fast tripping in case of short circuits.
  • 2UL/CSA Certification: Meets stringent safety standards for electrical protection.
  • 325kA Interrupting Rating: Provides high interrupting capacity for safe circuit disconnection.
  • 4Front Terminal Connection: Easy installation with front terminals for convenient access.
  • 5Rated for 175A at 240V AC/250V DC: Suitable for a wide range of industrial applications with high current and voltage requirements.
Product Details
A2N 250 TMF 175-1750 2p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
1SDL000183R0001 9AKK108467A6707
Product Net Width
70 mm
Product Net Height
150 mm
Product Net Depth / Length
60 mm
Product Net Weight
0.9 kg
Product Main Type
SACE FORMULA
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Electrical Durability
4000 cycle
Mechanical Durability
10000 cycle
Number of Poles
2P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Power Loss
at Rated Operating Conditions per Pole 10 W
Rated Current (In)
Main Circuit 175 A
Rated Impulse Withstand Voltage (Uimp)
6 kV
Rated Insulation Voltage (Ui)
690 V
Rated Operational Voltage
550 V AC 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 12.5 kA (480 V AC) 9 kA (500 V AC) 5 kA (250 V DC) 2 Poles in Series 5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 25 kA (480 V AC) 18 kA (500 V AC) 10 kA (250 V DC) 2 Poles in Series 10 kA
Rated Uninterrupted Current (Iu)
250 A
Release
TMF
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
A2
Terminal Connection Type
Front
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA066544R1

Specifications may be subject to change without notice