Product Model

OS125GF04F

In Stock
Last updated: 2025/5/1
ABB OS125GF04F

Selling Points

  • 1Reliable Performance: Designed for extreme conditions with self-cleaning contacts that maintain performance without damage.
  • 2Modular Design: Easy installation and maintenance with adjustable shafts and snap-on auxiliary contacts.
  • 3Enhanced Safety: Interlocking fuse covers prevent opening while in the "ON" position, reducing electric shock risk.
  • 4High Current Rating: Rated for up to 125 A, suitable for various voltage ranges including 380V to 415V and 500V to 690V.
  • 5Compliance Certificates: Meets NFC 63210, NFC 63211, and IEC 60269-2-1SEC III standards with DNV and CE declarations.
Product Details
OS125GF04F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Pollution Degree
3
Product Net Width
182 mm
Product Net Height
140 mm
Product Net Depth / Length
130 mm
Product Net Weight
1.8 kg
Cable Cross-Section
2.5 ... 25 mm²
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 125 A
Conventional Thermal Current (Ithe)
Fully Enclosed 125 A
Fourth Pole Type
Switched - Fusible Pole
Fuse Size
22x58
Fuse System
NFC
Handle Type
Handle and shaft not included
Mounting Type
Base mounting
Number of Poles
4
Operating Mode
Front Operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out, Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 4 W
Rated Conditional Short-Circuit Current (Inc)
(690 V) 80 kA
Rated Current (In)
Main Circuit 125 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Current AC-21A (Ie)
(500 V) 125 A (690 V) 125 A
Rated Operational Current AC-22A (Ie)
(500 V) 125 A (690 V) 125 A
Rated Operational Current AC-23A (Ie)
(500 V) 125 A (690 V) 125 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 37 kW (400 V) 55 kW (415 V) 55 kW (500 V) 75 kW (690 V) 110 kW
Rated Operational Voltage
Main Circuit 690 V AC
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 5 kiloampere rms
Standards
IEC 60947-3
Switches Operating Mechanism
04 (Left Side)
Terminal Type
Lug terminals
Terminal Width
20 mm
Tightening Torque
15 … 22 N·m
Tightening Torque
15 … 22 N·m
Object Classification Code
Q
ETIM 8
EC001040 - Fuse switch disconnector
ETIM 9
EC001040 - Fuse switch disconnector
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5291 >> Fuse switch disconnector
eClass
V11.1 : 27371401
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA115605R1001

Specifications may be subject to change without notice