Product Model

OT1250E22P

In Stock
Last updated: 2025/5/7
ABB OT1250E22P

Selling Points

  • 14-pole switch-disconnector with robust safety features.
  • 2IP65 protected handle and shaft for durability.
  • 3Suitable for low voltage applications up to 1000 VAC.
  • 4Front-operated mechanism with adjustable shaft for various installation depths.
  • 5Meets IEC 60947-1 standards with tightening torque of 50-75 N·m.
Product Details
OT1250E22P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301233D0201
Pollution Degree
3
Product Net Width
414.5 mm
Product Net Height
306 mm
Product Net Depth / Length
145.5 mm
Product Net Weight
19.7 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 1250 A
Conventional Thermal Current (Ithe)
Fully Enclosed 1250 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Color
Black
Handle Type
Handle and shaft included
Lock Type
Yes
Mechanical Durability
6000
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 29 W
Rated Conditional Short-Circuit Current (Inc)
(1250 A fuse, 415 V) 80 kA (1250 A fuse, 500 V) 100 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A
Rated Operational Power AC-23A (Pe)
(400 ... 415 V) 710 kW (500 V) 900 kW (690 V) 1200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 92 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 50 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism Between the Poles 22 (Between the Poles)
Terminal Type
Lug terminals
Terminal Width
50 mm
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3661706
Manufacturer ID
1SCA022871R5870