Product Model

OT160EAUA3T

In Stock
Last updated: 2025/4/30
ABB OT160EAUA3T

Selling Points

  • 1Space-saving solution for various applications.
  • 2Reliable operation in extreme conditions.
  • 3Non-fusible design ensures continuous protection.
  • 4Panel mountable for easy installation.
  • 5Built to withstand heavy use with a 20,000 operation cycle endurance.
Product Details
OT160EAUA3T
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP54
Pollution Degree
3
Product Net Width
400 mm
Product Net Height
600 mm
Product Net Depth / Length
230 mm
Product Net Weight
19 kg
Cable Cross-Section
120 mm²
Cable Entry Position
Down/Down
Cable Outlets Per Side
Blank / Open
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Degree of Protection
acc. to IEC 60529 IP54
Enclosure Material
Steel sheet
Handle Color
Black
Handle Type
Pistol handle
Maximum Mounted Auxiliary Contacts
2 NO, 1 NC
Mounted Auxiliary Contacts
1 NO, 1 NC
Number of Poles
3P
Pollution Degree
3
Position of Line Terminals
Bottom In - Bottom Out
Position of PE Terminals
Bottom In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 6.5 W
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 135 A (500 V) 125 A (690 V) 80 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 75 kW (500 V) 75 kW (690 V) 75 kW
Rated Operational Voltage
Main Circuit 750 V
Object Classification Code
Q
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
E-Number (Finland)
3642393
Manufacturer ID
1SCA022299R0690

Specifications may be subject to change without notice