Product Model

OT160EV03WP

In Stock
Last updated: 2025/5/4
ABB OT160EV03WP

Selling Points

  • 1Front-operated switch-disconnector with a wide phase distance.
  • 2Includes a black ON-OFF plastic handle and shaft as standard.
  • 3IP65 protected handle, padlockable in the OFF-position, and door interlock in the ON-position.
  • 4Adjustable shaft for various installation depths.
  • 5Suitable for distribution board installations with high reliability.
Product Details
OT160EV03WP
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301265D0201
Pollution Degree
3
Product Net Width
169.5 mm
Product Net Height
170 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.4 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 200 A
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Degree of Protection
Front IP00
Distance Between Phases
Wide phase distance
Handle Color
Black
Handle Type
Handle and shaft included
Lock Type
Yes
Mechanical Durability
20000
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 3.2 W
Rated Conditional Short-Circuit Current (Inc)
(315 A fuse, 500 V) 100 kA (355 A fuse, 690 V) 80 kA (250 A fuse, 690 V) 100 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 200 A (500 V) 200 A (690 V) 200 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 200 A (500 V) 200 A (690 V) 160 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 48 kW (400 ... 415 V) 88 kW (500 V) 112 kW (690 V) 144 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Special Functions
Wide phase distance
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch 03 (Left Side)
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3601368
Manufacturer ID
1SCA120517R1001

Specifications may be subject to change without notice