Product Model

OT250KAUC3TZ

In Stock
Last updated: 2025/5/7
ABB OT250KAUC3TZ

Selling Points

  • 1High Operational Power: Supports up to 132 kW AC-23A.
  • 2Robust Enclosure: Made of steel sheet with IP65 protection.
  • 3Multiple Contact Options: Includes 2 NO and 1 NC auxiliary contacts.
  • 4Versatile Installation: Bottom-in, bottom-out cable entry position.
  • 5Durable Design: Designed to withstand harsh industrial environments.
Product Details
OT250KAUC3TZ
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
400 mm
Product Net Height
800 mm
Product Net Depth / Length
230 mm
Product Net Weight
25.55 kg
Cable Entry Position
Bottom/Bottom
Cable Outlets Per Side
Blank / 2xC-flange, Knock-outs: 10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm
Connecting Capacity Main Circuit
Hole Diameter 8 mm Screw Clamp / PE Terminal 4pc,25 ... 120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 250 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Handle Color
Black
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK09
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
2 NO, 1 NC
Neutral Type
No neutral terminal
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
2
Number of Poles
3P
Pollution Degree
3
Position of Line Terminals
Bottom In - Bottom Out
Position of PE Terminals
Bottom In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 6.5 W
Rated Conditional Short-Circuit Current (Inc)
40.5 kA
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 132 kW (500 V) 160 kW (690 V) 200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Recommended Screw Driver
Main Circuit M8
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 22 N·m
Recommended Screw Driver
Main Circuit M8
Tightening Torque
Main Circuit 22 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
E-Number (Finland)
3642825
E-Number (Norway)
1429168
E-Number (Sweden)
3140648
Manufacturer ID
1SCA022340R1310

Specifications may be subject to change without notice