Product Model
OT400DLAA3AZ

Selling Points
- 1High-performance compact design for efficient electrical solutions.
- 2Non-fused disconnect switch with 400A current rating for reliable operation.
- 36 poles and 600VAC voltage rating for versatile applications.
- 4Panel mount design for easy installation in electrical cabinets.
- 5Compliant with IEC 60947-3 standards for safety and reliability.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Degree of Protection | acc. to IEC 60529 IP65 | Product Net Width | 400 mm |
Product Net Height | 800 mm | Product Net Depth / Length | 230 mm |
Product Net Weight | 22.03 kg | Cable Entry Position | Up/Down |
Cable Outlets Per Side | Open / Open | Connecting Capacity Main Circuit | Hole Diameter 10 mm Screw Clamp / PE Terminal 4pcs, 25â¦120 mm² |
Conventional Thermal Current (Ithe) | Fully Enclosed 400 A | Degree of Protection | acc. to IEC 60529 IP65 |
Enclosure Material | Steel sheet | Handle Color | Red / Yellow |
Handle Type | Pistol handle | Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC |
Mounted Auxiliary Contacts | 2 NO, 1 NC | Number of Poles | 3P |
Rated Conditional Short-Circuit Current (Inc) | 61.5 kA | Rated Impulse Withstand Voltage (Uimp) | 15 kV |
Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V | Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A |
Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A | Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 220 kW (500 V) 280 kW (690 V) 355 kW |
Rated Operational Voltage | Main Circuit 1000 V | Rated Short-Circuit Making Capacity (Icm) | (1000 V AC) 65 kA |
Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 15 kA | Standards | IEC 60947-1, -3 |
ETIM 8 | EC000216 - Switch disconnector | WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
Manufacturer ID | 1SCA022284R1770 |
Specifications may be subject to change without notice