Selling Points

  • 11-pole, front operated, base mounted switch-disconnector with black IP65 handle and shaft.
  • 2Includes terminal bolt kit for secure connections.
  • 3Meets IEC 60947-3 standards for reliability and safety.
  • 4Rated insulation voltage (Ui) up to 1000 volts, impulse withstand voltage (Uimp) up to 12 kilovolts.
  • 5Suitable for main circuit voltage of 1000 volts, with a rated short-time withstand current (Icw) of 15 kiloamperes for 1 second.
Product Details
OT400E01P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301266D0201
Pollution Degree
3
Product Net Width
103 mm
Product Net Height
185 mm
Product Net Depth / Length
107 mm
Product Net Weight
1.8 kg 3.9 lb
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 400 A
Conventional Thermal Current (Ithe)
Fully Enclosed 400 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Handle Color
Black
Handle Type
Handle and shaft included
Lock Type
Yes
Mechanical Durability
16000
Mounting Type
Base mounting
Number of Poles
1
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 10 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A (1000 V) 400 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 132 kW (400 ... 415 V) 230 kW (500 V) 280 kW (690 V) 400 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch 01 (Left Side)
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 30 … 44 N·m
Tightening Torque
acc. IEC 60947-1 30 … 44 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA022774R7010