Product Model

OTM1000E4M230C

In Stock
Last updated: 2025/5/3
ABB OTM1000E4M230C

Selling Points

  • 1Handles 1000 A at 40°C in free-air and fully enclosed conditions.
  • 2Rated for 12 kV impulse withstand voltage and 1000 V insulation voltage.
  • 3Includes inbuilt safety features and manual operation in emergency situations.
  • 4Compact size with direct mounted handle for easy operation.
  • 5Meets IEC 60947-3 standards and has no certification needed for CE, UL, or VDE.
Product Details
OTM1000E4M230C
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Pollution Degree
3
Product Net Width
586.5 mm
Product Net Height
306 mm
Product Net Depth / Length
153 mm
Product Net Weight
29 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 1000 A
Conventional Thermal Current (Ithe)
Fully Enclosed 1000 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Color
Black
Handle Type
Direct mounted handle
Lock Type
Yes
Mechanical Durability
6000
Motor Operational Voltage
220 ... 240 V AC
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 19 W
Rated Conditional Short-Circuit Current (Inc)
(1250 A fuse, 415 V) 80 kA (1250 A fuse, 500 V) 100 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 1000 A (500 V) 1000 A (690 V) 1000 A (1000 V AC) 1000 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 1000 A (500 V) 1000 A (690 V) 1000 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 1000 A (500 V) 1000 A (690 V) 1000 A
Rated Operational Power AC-23A (Pe)
(400 ... 415 V) 560 kW (500 V) 710 kW (690 V) 1000 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 92 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 50 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA115368R1001