Product Model
OTM40F3CMA230V

Selling Points
- 1Remote Operation: Operate the switch remotely or automatically for increased convenience and safety.
- 2High Durability: Designed for outdoor use, ensuring reliable performance in harsh environments.
- 3Safety Features: Provides safe and reliable switching between two power sources, reducing electrical failures and downtime.
- 4Versatile Applications: Suitable for power distribution, industrial systems, and backup power systems.
- 5Compliance Standards: Adheres to international safety and reliability standards, making it suitable for critical industrial applications.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Degree of Protection | Front IP20 | Pollution Degree | 3 |
Product Net Width | 230 mm 9.06 in | Product Net Height | 100 mm 3.94 in |
Product Net Depth / Length | 116 mm 4.57 in | Product Net Weight | 1.64 kg 3.62 lb |
Cable Cross-Section | 2.5 ... 16 mm² | Conventional Free-air Thermal Current (Ith) | Π= 40 °C 40 A |
Conventional Thermal Current (Ithe) | Fully Enclosed 40 A | Degree of Protection | Front IP20 |
Distance Between Phases | Standard | Handle Color | Black |
Handle Type | Direct mounted handle | Motor Operational Voltage | 110 ... 240 V AC/DC |
Mounting Type | Base mounting | Number of Poles | 3P |
Operating Mode | Front operated | Pollution Degree | 3 |
Position of Line Terminals | Top In - Bottom Out, Bottom In - Top Out | Power Loss | at Rated Operating Conditions per Pole 1.6 W |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 800 V |
Rated Operational Current AC-21A (Ie) | (380 ... 415 V) 40 A (500 V) 40 A (690 V) 40 A | Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 40 A (500 V) 40 A (690 V) 40 A |
Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 40 A (500 V) 40 A (690 V) 40 A | Rated Operational Current AC-31B (Ie) | (380 ... 415 V) 40 A |
Rated Operational Current AC-33B (Ie) | (380 ... 415 V) 40 A | Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 18.5 kW (500 V) 22 kW (690 V) 37 kW |
Rated Operational Voltage | Main Circuit 800 V | Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 2.5 kiloampere rms |
Switches Operating Mechanism | Mechanism at the End of the Switch | Terminal Type | Screw Terminals |
Tightening Torque | acc. IEC 60947-1 6 N·m | Transition Type | Open |
Tightening Torque | acc. IEC 60947-1 6 N·m | Object Classification Code | Q |
ETIM 8 | EC000216 - Switch disconnector | ETIM 9 | EC000216 - Switch disconnector (low voltage) |
UNSPSC | 39122214 | IDEA Granular Category Code (IGCC) | 5208 >> Controller switch |
eClass | V11.1 : 27371403 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
E-Number (Finland) | 3601226 | Manufacturer ID | 1SCA120096R1001 |
Specifications may be subject to change without notice