Product Model

T1B 160 TMD16-500 4p F FC Cu (1?à¨′70mm2)

In Stock
Last updated: 2025/5/6
ABB T1B 160 TMD16-500 4p F FC Cu (1?à¨′70mm2)

Selling Points

  • 1High short-circuit breaking capacity up to 16 kA.
  • 2Advanced protection with thermomagnetic and electronic trip units.
  • 3Compact dimensions with a net width of 76mm and net height of 130mm.
  • 4Suitable for 4-pole configurations with front terminals for copper cables.
  • 5Meets IEC 60947 standards for reliability and safety.
Product Details
T1B 160 TMD16-500 4p F FC Cu (1?à¨′70mm2)
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
102 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.3 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 1,5 W
Rated Current (In)
16 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 25 kA (230 V AC) 25 kA (380 V AC) 16 kA (415 V AC) 16 kA (440 V AC) 10 kA (500 V AC) 8 kA (690 V AC) 3 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 2.5 kA (230 V AC) 2.5 kA (380 V AC) 16 kA (415 V AC) 16 kA (440 V AC) 10 kA (500 V AC) 8 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 16 kA (250 V DC) 3 Poles in Series 20 kA (500 V DC) 3 Poles in Series 16 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
B
Standards
IEC 60947
Sub-type
T1
Terminal Connection Type
Fixed Circuit-Breakers Front for Copper Cables
Test Voltage Max (Utest)
3000 V
Object Classification Code
Q
Manufacturer ID
1SDA063520R1

Specifications may be subject to change without notice