Product Model

T1C 160 TMD50-500 4p F FC Cu (1?à¨′70mm2)

In Stock
Last updated: 2025/5/3
ABB T1C 160 TMD50-500 4p F FC Cu (1?à¨′70mm2)

Selling Points

  • 1High electrical durability with 8000 operations under load.
  • 2Compact dimensions: 130 mm x 101.6 mm x 70 mm.
  • 3Advanced thermal-magnetic protection for reliable short-circuit performance.
  • 4Rated for 160 A uninterrupted current and 50 A trip current.
  • 5Compliant with IEC 60947 standards for safety and efficiency.
Product Details
T1C 160 TMD50-500 4p F FC Cu (1?à¨′70mm2)
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
102 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.3 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 3,7 W
Rated Current (In)
50 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 30 kA (230 V AC) 30 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 11,25 kA (500 V AC) 7,5 kA (690 V AC) 3 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 4 kA (230 V AC) 4 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 15 kA (500 V AC) 10 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (250 V DC) 3 Poles in Series 30 kA (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
C
Standards
IEC 60947
Sub-type
T1
Terminal Connection Type
Fixed Circuit-Breakers Front for Copper Cables
Test Voltage Max (Utest)
3000 V
Object Classification Code
Q
Manufacturer ID
1SDA063533R1

Specifications may be subject to change without notice