Product Model

T1N 160 TMD80-800 3p F FC Cu (1?à¨′70mm2)

In Stock
Last updated: 2025/4/29
ABB T1N 160 TMD80-800 3p F FC Cu (1?à¨′70mm2)

Selling Points

  • 1High Performance Protection: Provides reliable and efficient protection for electrical systems.
  • 2Thermomagnetic Release: Combines thermal and magnetic trip units for adjustable and fixed thresholds.
  • 33-Pole Configuration: Suitable for three-phase applications, ensuring balanced protection.
  • 4Front Cable Connection: Easy installation with front cable connection terminals.
  • 5Durable Construction: Built with high-quality materials for long-lasting performance.
Product Details
T1N 160 TMD80-800 3p F FC Cu (1?à¨′70mm2)
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
1SDL000140R0
Product Net Width
76 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Suitable For
T1
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 4,8 W
Rated Current (In)
80 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 37,5 kA (230 V AC) 37,5 kA (380 V AC) 27 kA (400 V AC) 27 kA (415 V AC) 27 kA (440 V AC) 11 kA (500 V AC) 7,5 kA (690 V AC) 3 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 5 kA (230 V AC) 5 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 22 kA (500 V AC) 15 kA (690 V AC) 6 kA (250 V DC) 2 Poles in Series 36 kA (250 V DC) 3 Poles in Series 40 kA (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC 60947
Sub-type
T1
Terminal Connection Type
Fixed Circuit-Breakers Front for Copper Cables
Test Voltage Max (Utest)
3000 V
Test Voltage at Industrial Frequency for 1 Minute
3000 V
Object Classification Code
Q
UNSPSC
39121100
Manufacturer ID
1SDA050921R1

Specifications may be subject to change without notice