Product Model
T5S 600 UL/CSA PR222DS/P-LSI 600 3p F F

Selling Points
- 1UL/CSA Certification: Meets stringent safety standards for reliable operation.
- 2Electronic Trip Unit: Advanced LSIG trip unit ensures precise and fast tripping.
- 3Three-Pole Design: Suitable for 3-phase applications, providing comprehensive protection.
- 4High Current Rating: Handles up to 600A, making it suitable for demanding electrical systems.
- 5Compact Design: Easy to install and integrate into various electrical panels.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1056 9AKK108467A6707 | Product Net Width | 140 mm |
Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 5.1 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T5 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Mechanical Durability | 20000 cycle 120 cycles per hour |
Number of Poles | 3 | Power Loss | at Rated Operating Conditions per Pole 37.1 W |
Rated Current (In) | 600 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 600 V AC |
Rated Uninterrupted Current (Iu) | 600 A | Release | PR222DS/P-LSI |
Release Type | EL | Short-Circuit Performance Level | S |
Standards | UL | Sub-type | T5 |
Terminal Connection Type | Fixed Circuit-Breakers Front | Test Voltage Max (Utest) | 3500 V |
Interrupting Rating acc. to UL489 | (240 V AC) 100 kA (480 V AC) 35 kA (600 V AC) 25 kA | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA061840R1 |
Specifications may be subject to change without notice