Product Model
T6L800 TMA800-8000 4p F F 1000VDC JUMPER

Selling Points
- 1High Voltage Rating: 1000V AC/DC for versatile applications.
- 2Robust Construction: Designed with a thermal-magnetic release for reliable short-circuit protection.
- 3High Current Capacity: Handles up to 800A in main circuits.
- 4Durable Performance: Withstands 5000 electrical cycles and 20,000 mechanical cycles.
- 5Compliance with Standards: Meets IEC 60947 standards for safety and performance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1058 9AKK108467A6707 | Product Net Width | 280 mm |
Product Net Height | 268 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 12 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T6 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Electrical Durability | 5000 cycle 60 cycles per hour |
Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 4P |
Rated Current (In) | 800 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 1000 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (1000 V AC) 6 kA (1150 V AC) 12.5 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (1000 V AC) 12 kA (1000 V DC) 50 kA |
Rated Uninterrupted Current (Iu) | 800 A | Release | TMA |
Release Type | TM | Short-Circuit Performance Level | L |
Standards | IEC | Terminal Connection Type | Fixed Circuit-Breakers Front |
ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
Manufacturer ID | 1SDA082626R1 |
Specifications may be subject to change without notice