Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1058 9AKK108467A6707 | Product Net Width | 210 mm |
Product Net Height | 268 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 9.5 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T6 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Mechanical Durability | 20000 cycle 120 cycles per hour |
Number of Poles | 3P | Power Loss | at Rated Operating Conditions per Pole 31 W |
Rated Current (In) | 800 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 600 V AC 600 V DC |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (240 V AC) 200 kA (480 V AC) 100 kA (600 V AC) 42 kA (500 V DC) 2 Poles in Series 65 kA (600 V DC) 3 Poles in Series 50 kA | Rated Uninterrupted Current (Iu) | 800 A |
Release | TMA | Release Type | TM |
Short-Circuit Performance Level | L | Standards | UL |
Sub-type | T6 | Terminal Connection Type | Fixed Circuit-Breakers Front |
Test Voltage Max (Utest) | 3500 V | Interrupting Rating acc. to UL489 | (240 V AC) 200 kA (480 V AC) 100 kA (600 V AC) 42 kA (500 V DC) 2 Poles in Series 65 kA (600 V DC) 3 Poles in Series 50 kA |
ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
Manufacturer ID | 1SDA061664R1 |