Product Model
T6V 800 PR221DS-I In=800 4p F F

Selling Points
- 1Handles up to 800 A with a rated uninterrupted current (Iu) of PR221DS-I.
- 2Features a solid-state release mechanism for fast and reliable short-circuit interruption.
- 3Equipped with front terminals for easy installation and maintenance.
- 4Meets IEC standards for performance and safety.
- 5Built with double insulation and oversized insulation for enhanced electrical safety and durability.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1058 9AKK108467A6707 | Product Net Width | 280 mm |
Product Net Height | 268 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 12 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T6 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Electrical Durability | 5000 cycle 60 cycles per hour |
Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 4P |
Power Loss | at Rated Operating Conditions per Pole 32 W | Rated Current (In) | 800 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 690 V AC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 65 kA (690 V AC) 30 kA |
Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 10 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 150 kA (400 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 120 kA (500 V AC) 85 kA (690 V AC) 40 kA |
Rated Uninterrupted Current (Iu) | 800 A | Release | PR221DS-I |
Release Type | EL | Short-Circuit Performance Level | V |
Standards | IEC | Sub-type | T6 |
Terminal Connection Type | Fixed Circuit-Breakers Front | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA069433R1 |
Specifications may be subject to change without notice