Product Model

XT1H 125 TMF 100-1000 4p F F UL/CSA

In Stock
Last updated: 2025/4/28
ABB XT1H 125 TMF 100-1000 4p F F UL/CSA

Selling Points

  • 1High-Performance Protection: Offers advanced thermal and magnetic protection for reliable short-circuit and overload protection.
  • 2Comprehensive Compliance: Meets UL 489 and CSA C22.2 standards, ensuring compliance with international safety regulations.
  • 3Versatile Connectivity: Features ring-lug or bar connections for easy installation and customization.
  • 4Advanced Metering Capabilities: Trip units measure electrical parameters with 1% accuracy, enhancing energy management strategies.
  • 5Upgradeable Design: Ekip Touch and Hi-Touch trip units can be upgraded via ABB Ability MarketplaceTM for future functionalities.
Product Details
XT1H 125 TMF 100-1000 4p F F UL/CSA
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH001295R0080
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 7 W
Rated Current (In)
100 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
1000 A
Rated Operational Voltage
600Y/347 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600Y/347 V
Recommended Screw Driver
Main Circuit M6
Release
TMF
Release Type
TM
Setting Range
100 A
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 100 kA (480 V AC) 65 kA (600Y / 347 V AC) 25 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 4 Poles in Series Kind 50 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074721R1

Specifications may be subject to change without notice