Product Model
XT1H160 TMD63/630 FFC 3P

Selling Points
- 1High-Performance Protection: The XT1H160 TMD63/630 3P FF circuit breaker offers robust protection against short circuits and overloads.
- 2Thermomagnetic Release: Equipped with a thermomagnetic release, ensuring reliable operation under various conditions.
- 3Versatile Applications: Suitable for protecting generators, motors, and communication systems.
- 4Extended Product Type: Meets IEC standards and is compatible with various fieldbus and IP communication protocols.
- 5Simplified Installation: Features Bluetooth and Ekip connectivity for simplified installation and real-time data analysis via the ABB AbilityTM Cloud platform.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Main Type | SACE Tmax XT |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | F | Current Type | AC/DC |
Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
Number of Poles | 3P | Power Loss | at Rated Operating Conditions per Pole 4.3 W |
Rated Current (In) | 63 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 800 V | Rated Operational Voltage | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 75 kA (230 V AC) 75 kA (240 V AC) 75 kA (380 V AC) 52.5 kA (415 V AC) 37.5 kA (440 V AC) 32.5 kA (500 V AC) 25 kA (525 V AC) 17.5 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 52.5 kA (500 V DC) 3 Poles in Series 52.5 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 35 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA |
Rated Uninterrupted Current (Iu) | 160 A | Release | TMD |
Release Type | TM | Remarks | ATLAS |
Short-Circuit Performance Level | H | Standards | IEC60947-2 GB/T 14028.2 |
Sub-type | XT1 | Terminal Connection Type | Front for Copper Cables |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 2TFH100162R1001 |
Specifications may be subject to change without notice