Product Model

XT2H 160 Ekip Dip LSIG In=100A 4p F F

In Stock
Last updated: 2025/4/28
ABB XT2H 160 Ekip Dip LSIG In=100A 4p F F

Selling Points

  • 1Equipped with electronic trip units (Ekip DIP LSIG) for precise overload and short-circuit protection.
  • 2Rated for 100A with a frame current rating of 160 AF, suitable for demanding applications.
  • 3Meets IEC 60947-1 and IEC 60947-2 standards, ensuring safety and reliability.
  • 4Supports ring-lug or bar connections for flexible installation options.
  • 5Designed for 8000 operations under load and 25000 operations at no load, ensuring long-lasting performance.
Product Details
XT2H 160 Ekip Dip LSIG In=100A 4p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1002
Current Type
AC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 4.20 W
Rated Current (In)
100 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA100083R1

Specifications may be subject to change without notice