Product Model

XT2L 125 MCP Iu=100 3p F F UL/CSA

In Stock
Last updated: 2025/5/1
ABB XT2L 125 MCP Iu=100 3p F F UL/CSA

Selling Points

  • 1High-Performance Circuit Breaker: Designed for AC Ekip-I R 125 A applications with a solid-state release.
  • 2Compliant with UL/CSA Standards: Meets UL and CSA standards for electrical safety and durability.
  • 3Extended Product Life: Zero Waste To Landfill Validation available, promoting environmental sustainability.
  • 4Robust Mechanical Durability: Withstood 25000 cycles per hour and 240 cycles per hour at 600V AC.
  • 5Versatile Terminal Connection: Front terminal connection type with bolt terminals, ensuring easy installation and maintenance.
Product Details
XT2L 125 MCP Iu=100 3p F F UL/CSA
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Circuit Breaker Type to be Associated
Motor Protection
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Current Type
AC/DC
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 8.1 W
Rated Current (In)
100 A
Rated Frequency (f)
50 / 60 Hz
Rated Instantaneous Short-Circuit Current Setting (Ii)
300…1100 A
Rated Operational Voltage
600 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Release
MA
Release Type
M
Short-Circuit Performance Level
L
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Interrupting Rating acc. to UL489
(240 V AC) 200 kA (480 V AC) 100 kA (600 V AC) 35 kA (250 V DC) 2 Poles in Series 75 kA (500 V DC) 3 Poles in Series 75 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074898R1