Product Model

XT2L160 DC TMA80 FF 4P

In Stock
Last updated: 2025/5/7
ABB XT2L160 DC TMA80 FF 4P

Selling Points

  • 1Designed to handle high short-circuit currents up to 85 kA in DC configurations.
  • 2Ensures reliable operation with a mechanical durability of 25,000 operations.
  • 3Operates within a wide voltage range, including 250 V DC and 500 V DC configurations.
  • 4Equipped with thermomagnetic release (TMA) for efficient thermal management.
  • 5Meets IEC60947-2 standards for safety and performance.
Product Details
XT2L160 DC TMA80 FF 4P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle ;240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 5.8 W
Rated Current (In)
80 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
L
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA123559R1