Product Model
XT2L 160 Ekip Hi-Touch LSI R160 F F 3P

Selling Points
- 1High-Performance Solid-State Release: Ensures reliable and fast tripping in case of short circuits.
- 2Three-Pole Design: Suitable for three-phase AC applications, providing comprehensive protection.
- 3Rated for 690V AC: Compatible with a wide range of voltage requirements, ensuring versatility in electrical systems.
- 4160A Rated Current: Handles high current loads efficiently, making it suitable for demanding electrical setups.
- 5Compliant with EU Directives: Meets environmental standards, including RoHS compliance, for sustainable operation.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 1SDL000190R0001 | Product Net Width | 90 mm |
Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
Product Net Weight | 1.2 kg | Product Name | Moulded Case Circuit Breaker |
Product Type | CB | Version | F |
Current Type | AC | Electrical Durability | 8000 cycle 120 cycles per hour |
Mechanical Durability | 25000 cycle 240 cycles per hour | Number of Poles | 3P |
Power Loss | at Rated Operating Conditions per Pole 10.80 W | Rated Current (In) | 160 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 690 V AC 500 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA | Rated Uninterrupted Current (Iu) | 160 A |
Release | Ekip Hi-Touch LSI | Release Type | EL |
Short-Circuit Performance Level | L | Standards | IEC 60947-2 GB/T 14028.2 |
Sub-type | XT2 | Terminal Connection Type | Fixed Circuit-Breakers |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 2TFN000265A1001 |
Specifications may be subject to change without notice