Product Model

XT2L160 I R25 PMP 4P

In Stock
Last updated: 2025/4/30
ABB XT2L160 I R25 PMP 4P

Selling Points

  • 1High Performance: Designed to handle high currents and voltages, ensuring reliable operation in demanding electrical environments.
  • 2Advanced Protection: Equipped with thermomagnetic release (TMD) for enhanced short-circuit protection and safety.
  • 3Compact Design: Compact dimensions make it easy to integrate into various electrical systems without taking up too much space.
  • 4Compliance and Certifications: Meets international standards and certifications including IEC and UL, ensuring compliance with global regulations.
  • 5Durable Construction: Built with high-quality materials for long-lasting performance and minimal maintenance requirements.
Product Details
XT2L160 I R25 PMP 4P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
120.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
3.27 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 0.9 W
Rated Current (In)
25 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip I
Release Type
EL
Remarks
ATLAS
Short-Circuit Performance Level
L
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Plug-In Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100762R1001

Specifications may be subject to change without notice