Product Model

XT2L160 TMA40/400 PMP 3P

In Stock
Last updated: 2025/5/4
ABB XT2L160 TMA40/400 PMP 3P

Selling Points

  • 1Handles currents up to 400 A with a thermomagnetic release.
  • 2Ideal for three-phase electrical systems.
  • 3Easy installation with front terminals.
  • 4Designed to withstand 25,000 operations at 240 cycles per hour.
  • 5Meets IEC standards for safety and performance.
Product Details
XT2L160 TMA40/400 PMP 3P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC/DC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 4.4 W
Rated Current (In)
40 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
L
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Plug-In Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100801R1001

Specifications may be subject to change without notice