Product Model

XT2L160 TMD20/300 PMP 3P

In Stock
Last updated: 2025/5/5
ABB XT2L160 TMD20/300 PMP 3P

Selling Points

  • 1Built to withstand heavy usage, ensuring long-term reliability.
  • 2Rated for 150 kA at 220-240 V AC and 85 kA at 250 V DC.
  • 3Suitable for AC/DC currents with a high number of operations (up to 25,000 cycles).
  • 4Easy to install with bolt terminals and a tightening torque of 6 N·m.
  • 5Meets international safety standards for electrical equipment.
Product Details
XT2L160 TMD20/300 PMP 3P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC/DC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 1.9 W
Rated Current (In)
20 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
L
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Plug-In Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100820R1001