Product Model

XT2N160 DC TMA125 FF 4P

In Stock
Last updated: 2025/5/1
ABB XT2N160 DC TMA125 FF 4P

Selling Points

  • 1High electrical durability with 120 cycles per hour and 8000 cycles.
  • 2Robust short-circuit performance with up to 65 kA at various voltage levels.
  • 3Compatible with AC/DC currents and rated for 690 V AC and 500 V DC.
  • 4Thermomagnetic release (TMA) ensures reliable operation under short-circuit conditions.
  • 5Meets IEC standards for safety and performance in power distribution systems.
Product Details
XT2N160 DC TMA125 FF 4P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle ;240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 11.4 W
Rated Current (In)
125 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA123517R1

Specifications may be subject to change without notice