Product Model

XT2S160 DC TMA63 FF 3P

In Stock
Last updated: 2025/5/1
ABB XT2S160 DC TMA63 FF 3P

Selling Points

  • 1Handles up to 50 kA in DC and AC applications.
  • 2Ensures reliable operation with a thermomagnetic release mechanism.
  • 3Convenient front terminal connection for easy installation.
  • 4Built to withstand 120 cycles per hour and 8000 cycles in total.
  • 5Meets EU Directive 2011/65/EU and Amendment 2015/863 for RoHS compliance.
Product Details
XT2S160 DC TMA63 FF 3P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle ;240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 4.85 W
Rated Current (In)
63 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
S
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA123525R1

Specifications may be subject to change without notice