Product Model

XT2X 125 TMF 60-600 3p F F UL/CSA

In Stock
Last updated: 2025/5/2
ABB XT2X 125 TMF 60-600 3p F F UL/CSA

Selling Points

  • 1The XT2X 125 TMF features a thermal-magnetic trip unit for reliable and efficient circuit protection.
  • 2Meets UL and CSA standards, ensuring compliance with North American safety regulations.
  • 3Designed to handle high short-circuit currents up to 18 kA at 600Y/347 V AC.
  • 4Easy front terminal connection with bolt terminals for straightforward installation.
  • 5Compact dimensions (8.19 in width, 5.71 in height, 5.12 in depth) for space-efficient installations.
Product Details
XT2X 125 TMF 60-600 3p F F UL/CSA
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 4.4 W
Rated Current (In)
60 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
600 A
Rated Operational Voltage
600 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600 V
Release
TMF
Release Type
TM
Setting Range
60 A
Short-Circuit Performance Level
X
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Interrupting Rating acc. to UL489
(240 V AC) 200 kA (480 V AC) 200 kA (600 V AC) 42 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA081951R1

Specifications may be subject to change without notice