Product Model

XT2X160 DC TMD25 FF 4P

In Stock
Last updated: 2025/5/8
ABB XT2X160 DC TMD25 FF 4P

Selling Points

  • 1High-Performance Circuit Breaker: Designed for reliable operation in industrial settings.
  • 2Thermomagnetic Release: Ensures safe and efficient tripping in case of overcurrent conditions.
  • 3Front Terminals: Easy installation and maintenance with front-accessible terminals.
  • 44-Pole Configuration: Suitable for a variety of electrical applications requiring four poles.
  • 5Durable Construction: Built to withstand 120 cycles per hour and 8000 total cycles.
Product Details
XT2X160 DC TMD25 FF 4P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle ;240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 2.00 W
Rated Current (In)
25 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 100 kA (500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 100 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
X
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA123576R1