Product Model
XT3N 250 TMG250/750 P MP 4P N=100%

Selling Points
- 1High-Performance Protection: Designed for generator protection with a thermomagnetic release (TMG) for reliable operation.
- 2Rated Current of 250 A: Handles up to 250 A of current, ensuring efficient power distribution.
- 3Breaking Capacity of 36 kA: Provides robust short-circuit breaking capacity, ensuring safety in high-voltage applications.
- 4Front Terminal Connection: Easy installation with front terminals for straightforward connections.
- 5Compliant with IEC Standards: Meets international safety standards, ensuring compliance and reliability in your electrical setup.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Net Width | 140.0 mm |
Product Net Height | 150.0 mm | Product Net Depth / Length | 70.0 mm |
Product Net Weight | 4.1 kg | Product Main Type | SACE Tmax XT |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | P | Current Type | AC/DC |
Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
Number of Poles | 4P | Power Loss | at Rated Operating Conditions per Pole 21.4 W |
Rated Current (In) | 250 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 800 V | Rated Operational Voltage | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 37.5 kA (230 V AC) 37.5 kA (240 V AC) 37.5 kA (380 V AC) 27 kA (415 V AC) 27 kA (440 V AC) 18.75 kA (500 V AC) 15 kA (525 V AC) 9.75 kA (690 V AC) 3.75 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 25 kA (500 V AC) 20 kA (525 V AC) 13 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
Rated Uninterrupted Current (Iu) | 250 A | Release | TMG |
Release Type | TM | Short-Circuit Performance Level | N |
Standards | IEC60947-2 GB/T 14028.2 | Sub-type | XT3 |
Terminal Connection Type | Plug-In Circuit-Breakers | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Manufacturer ID | 2TFH101323R1001 |
Specifications may be subject to change without notice