Product Model

XT4N160 LSIG R40 WMP 4P

In Stock
Last updated: 2025/5/1
ABB XT4N160 LSIG R40 WMP 4P

Selling Points

  • 1The XT4N160 LSIG R40 WMP 4P circuit breaker offers superior electrical durability with 120 cycles per hour and 8000 cycles, ensuring reliable operation in demanding environments.
  • 2Equipped with solid-state release technology, this circuit breaker provides fast and precise short-circuit interruption, ensuring quick recovery and minimal downtime.
  • 3Designed with front terminals and a solid-state release, the XT4N160 LSIG R40 WMP 4P offers enhanced safety and reduced risk of electrical shock, meeting stringent safety standards.
  • 4Compatible with the Tmax XT range, this circuit breaker integrates seamlessly into existing electrical systems, ensuring smooth operation and minimal disruption.
  • 5Meets IEC standards and is CE compliant, ensuring that the product adheres to international safety and performance regulations, providing peace of mind for users.
Product Details
XT4N160 LSIG R40 WMP 4P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
140.0 mm
Product Net Height
160.0 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
6.76 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
W
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 0.7 W
Rated Current (In)
40 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip LSIG
Release Type
EL
Remarks
ATLAS
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT4
Terminal Connection Type
Withdrawable Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH103006R1001