Product Model

XT4N250 EKIP M-LRIU R200 FF 3P

In Stock
Last updated: 2025/5/1
ABB XT4N250 EKIP M-LRIU R200 FF 3P

Selling Points

  • 1Operates at 120 cycles per hour and up to 8000 cycles.
  • 2Withstands 240 cycles per hour and up to 25,000 cycles.
  • 3Low power loss at rated operating conditions per pole (16.4 W).
  • 4Meets UL and CSA standards for safety and reliability.
  • 5Suitable for power distribution in various industrial settings.
Product Details
XT4N250 EKIP M-LRIU R200 FF 3P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
105.0 mm
Product Net Height
160.0 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
2.5 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
3P
Rated Current (In)
200 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Uninterrupted Current (Iu)
250 A
Release
Ekip M-LRIU
Release Type
EL
Remarks
ATLAS
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT4
Terminal Connection Type
Front
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100463R1001

Specifications may be subject to change without notice