Selling Points

  • 1High Electrical Durability: 120 cycles per hour, 8000 cycles total.
  • 2Mechanical Durability: 240 cycles per hour, 25,000 cycles total.
  • 3Efficient Operation: 15 ms opening time with SOR and UVR.
  • 4Compliance with Standards: UL/CSA certified for safety and reliability.
  • 5Suitable for Power Distribution: Ideal for busbar connections up to 200 mm².
Product Details
XT4N250 EKIP M-LRIU R200 PMP 3P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
105.0 mm
Product Net Height
160.0 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
4.19 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
3P
Rated Current (In)
200 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Uninterrupted Current (Iu)
250 A
Release
Ekip M-LRIU
Release Type
EL
Remarks
ATLAS
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT4
Terminal Connection Type
Plug-In Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH103795R1001

Specifications may be subject to change without notice