Product Model

XT4N 250 Ekip Touch Measuring LSI In=250A 3p F F

In Stock
Last updated: 2025/5/1
ABB XT4N 250 Ekip Touch Measuring LSI In=250A 3p F F

Selling Points

  • 1Advanced Electronic Trip Unit: The XT4N 250 Ekip Touch Measuring LSI features an electronic trip unit for precise overload and short-circuit protection.
  • 2LCD Display for Real-Time Monitoring: Equipped with an LCD display, this circuit breaker provides real-time monitoring of phase-to-phase voltage, phase sequence, frequency, active power, reactive power, apparent power, and power factor.
  • 3Compliance with UL/CSA Standards: Meets UL 489 and CSA C22.2 standards for safety and reliability in power distribution systems.
  • 4High Short-Circuit Breaking Rating: Capable of breaking short circuits up to 65kA at 240Vac, ensuring robust protection against electrical faults.
  • 5Adjustable Protection Settings: Offers adjustable protection settings for overload and short-circuit protection, allowing customization for specific application needs.
Product Details
XT4N 250 Ekip Touch Measuring LSI In=250A 3p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
105.0 mm
Product Net Height
160.0 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
2.5 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 16.4 W
Rated Current (In)
250 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Uninterrupted Current (Iu)
250 A
Release
Ekip Touch Measuring LSI
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT4
Terminal Connection Type
Front
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFN001052A1001

Specifications may be subject to change without notice