Product Model

FLT-PLUS CTRL-3.0/I

In Stock
Last updated: 2025/5/1
Phoenix Contact FLT-PLUS CTRL-3.0/I

Selling Points

  • 1Compact design: 35.5 mm width, 150 mm height, and 80.5 mm depth.
  • 2High reliability: V0 flammability rating according to UL 94.
  • 3Versatile application: Compatible with CQM1 PLC and 16-point contact output.
  • 4Enhanced protection: Surge arrestor/suppressor for reliable electrical protection.
  • 5Cost-effective solution: Available for purchase as a surplus item starting at £149.14.
Product Details
FLT-PLUS CTRL-3.0/I
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Combination type
IEC test classification
I T1
EN type
T1
IEC power supply system
TT TN-C TN-S IT
Type
DIN rail module, one-piece 
Number of positions
1
Surge protection fault message
optical
Overvoltage category
III
Pollution degree
2
Nominal frequency f
50 Hz 60 Hz
Nominal voltage U
230 V AC (400 V AC)
Connection method
Screw connection
Screw thread
M6
Tightening torque, min
8 Nm
Stripping length
19 mm
Conductor cross section flexible min.
16 mm²
Conductor cross section flexible max.
35 mm²
Conductor cross section, rigid min.
10 mm²
Conductor cross section, rigid max.
50 mm²
Width
35.5 mm
Height
150 mm
Depth
80.5 mm
Horizontal pitch
2 Div.
Flammability rating according to UL 94
V0
Housing material
PA-GF
Open side panel
No
Direction of action
1L-N/PE
Nominal frequency f
50 Hz 60 Hz
Maximum continuous voltage U
440 V AC
Maximum continuous operating voltage U
440 V AC
Maximum continuous operating voltage U
440 V AC
Residual current I
≤ 3 mA
Standby power consumption P
≤ 1.32 VA
Nominal discharge current I
50 kA
Nominal discharge current I
50 kA
Nominal discharge current I
50 kA
Maximum discharge current I
50 kA
Impulse discharge current (10/350) µs, charge
25 As
Impulse discharge current (10/350) µs, specific energy
625 kJ/Ω
Impulse discharge current (10/350) µs, peak value l
50 kA
Follow current interrupt rating I
25 kA (440 V AC) 50 kA (350 V AC)
Voltage protection level U
≤ 3 kV
Voltage protection level U
≤ 3 kV
Voltage protection level U
≤ 3 kV
Front of wave sparkover voltage at 6 kV (1.2/50) µs
≤ 3 kV
Response time t
≤ 100 ns
Response time t
≤ 100 ns
Response time t
≤ 100 ns
Max. backup fuse with branch wiring
500 A (NH-gL)
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 85 °C
Permissible humidity (operation)
≤ 95 %
Standards/regulations
EN 60664-1 / EN 61643-11
Standards/regulations
IEC 61643-1 DIN EN 61643-11 DIN EN 61643-11/A11
Standards/specifications
IEC 61643-1
Note
2005
Standards/specifications
DIN EN 61643-11
Note
2002
Standards/specifications
DIN EN 61643-11/A11
Note
2007
Mounting type
DIN rail: 35 mm

Specifications may be subject to change without notice