Product Model

IB IL 24 LPSDO 8-PAC

In Stock
Last updated: 2025/4/28
Phoenix Contact IB IL 24 LPSDO 8-PAC

Selling Points

  • 1Safety-Certified Design: Meets SIL 3 standards for functional safety and SIL CL 3 according to EN 62061.
  • 2Versatile Connectivity: Compatible with INTERBUS, EtherNet/IP, CANopen, and other industrial protocols.
  • 3Robust Protection: IP20 protection and overload/short-circuit protection for digital outputs.
  • 4Flexible Output Options: Four safe digital outputs for two-channel assignment or eight for single-channel assignment.
  • 5High-Speed Transmission: Set transmission speed to 500 kbaud or 2 Mbaud for efficient data transfer.
Product Details
IB IL 24 LPSDO 8-PAC
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
Color
yellow
No. of channels
2
Connection method
Inline data jumper
Transmission speed
500 kbps / 2 Mbps
Connection to I/O modules
max. 3 (safe digital input modules)
Logic memory
6 kByte
ID code (dec.)
199
ID code (hex)
C7
Length code (hex)
12
Length code (dec)
18
Process data channel
30 Byte
Input address area
max. 30 Byte ((Operating mode: SafetyBridge))
Output address area
max. 30 Byte ((Operating mode: SafetyBridge))
Register length
32 Byte
Required parameter data
1 Byte ((Operating mode: SafetyBridge))
Required configuration data
5 Byte ((Operating mode: SafetyBridge))
Output name
Digital outputs
Connection method
Spring-cage connection
Connection technology
2-, 3-, 4-conductor
Number of outputs
4 (for 2-channel assignment) 8 (for 1-channel assignment) 8
Protective circuit
Overload protection, short-circuit protection of outputs
Output voltage
24 V DC (U
Output current
max. 6 A (Total current of all outputs, -25 °C ... 50 °C) max. 4 A (Total current of all outputs, >50 °C ... 55 °C)
Maximum output current per group
3 A
Maximum output current per channel
2 A
Nominal output voltage
24 V DC
Nominal load, inductive
see safety data
Nominal load, lamp
see safety data
Nominal load, ohmic
see safety data
Behavior with inductive overload
Output can be destroyed
Product type
I/O component
Product family
Inline
Application
Functional safety
Type
modular
Diagnostics messages
Short-circuit or overload of the digital outputs Error message in diagnostics code (bus) and display by means of the LED on the motor
Article revision
07
Maximum power dissipation for nominal condition
150 W
Transmission medium
Copper
Supply voltage
7.5 V DC (see safety data)
Current draw
max. 230 mA (see safety data)
Supply voltage
24 V DC (see safety data)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 6.03 A typ. 30 mA (all outputs set including actuator current)
Supply voltage
24 V (see safety data)
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O)
500 V AC, 50 Hz, 1 min
Test voltage: 24 V supply (I/O) / functional ground
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
pluggable
yes
Connection method
Spring-cage connection
Conductor cross section rigid
0.2 mm² ... 1.5 mm²
Conductor cross section flexible
0.2 mm² ... 1.5 mm²
Conductor cross section AWG
24 ... 16
Connection method
Spring-cage connection
Conductor cross section, rigid
0.2 mm² ... 1.5 mm²
Conductor cross section, flexible
0.2 mm² ... 1.5 mm²
Conductor cross section AWG
24 ... 16
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
80 hPa ... 108 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)
66 hPa ... 108 kPa (up to 3500 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Permissible humidity (operation)
10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.)
Permissible humidity (storage/transport)
10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice