Product Model

IB IL 24 MUX MA-PAC

In Stock
Last updated: 2025/4/30
Phoenix Contact IB IL 24 MUX MA-PAC

Selling Points

  • 1High I/O Capacity: Supports up to 63 I/O terminals and 512 digital or 32 analog I/Os.
  • 2Robust Connectivity: Equipped with an inline shield connector for RS-485 transmission and an inline data jumper for local bus connections.
  • 3Flexible Power Supply: Can be supplied with all required 24 V voltages, including main, segment, and analog module supplies.
  • 4Alarm Output: Includes a floating alarm output with an N/C relay contact for connecting alarm signals.
  • 5Compact Design: Measures 48.8 mm wide, 135 mm high, and 71.5 mm deep, making it ideal for space-constrained applications.
Product Details
IB IL 24 MUX MA-PAC
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
48.8 mm
Height
135 mm
Depth
71.5 mm
Note on application
Only for industrial use
Connection method
Inline shield connector
Transmission physics
RS-485
Connection method
Inline data jumper
Transmission speed
500 kbps
Number of local bus devices that can be connected
32 (without additional power terminal block, observe allowable total current consumption)
Number of devices with parameter channel
0
Number of supported branch terminals with remote bus branch
0
ID code (hex)
none
Contact switching type
N/C contact
Contact connection type
floating contacts
Switching voltage
typ. 24 V DC max. 150 V max. 125 V AC
Switching current
max. 1 A
Switching capacity
max. 30 W max. 60 VA
Product type
I/O component
Product family
Inline
Type
modular
Article revision
10
Overvoltage category
II
Pollution degree
2 (in accordance with EN 50178)
Maximum power dissipation for nominal condition
3 W
Protective circuit
Surge protection (segment supply, main supply, field multiplexer supply); Input protective diodes (can be destroyed by permanent overload)Pulse loads up to 1500 W are short circuited by the input protective diode. Protection against polarity reversal (segment supply/main supply); Parallel diodes for protection against polarity reversal; in the event of an error the high current flowing through the diodes causes the fuse connected upstream to blow. Protection against polarity reversal (field multiplexer supply); Serial diode in the lead path of the power supply unit; in the event of an error only a low current flows. In the event of an error, no fuse trips within the external power supply unit.
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 1.25 A (with max. number of connected I/O terminal blocks) typ. 60 mA (without connected Inline I/O terminals)
Supply voltage
7.5 V DC ±5 %
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Test voltage: RS-485 interface / supply voltage
500 V AC
Test voltage: RS-485 interface / local bus
500 V AC
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice