Product Model
IB IL PM 3P/N/EF-2MBD-PAC

Selling Points
- 1Supports up to 2 Mbps transmission speed for efficient inline data transfer.
- 2Designed for precise power measurement with 0.25% accuracy and up to 1 W power dissipation.
- 3Meets IP20 protection standards according to IEC 60529, ensuring safe operation in various environments.
- 4Compatible with inline connectors and supports current measuring inputs up to 5 A AC.
- 5Features internal scanning values synchronized with mains frequency (20 Hz - 100 Hz) for reliable process data updates.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 48.8 mm | Height | 119.8 mm |
Depth | 71.5 mm | Note on dimensions | Housing dimensions |
Connection method | Inline data jumper | Transmission speed | 2 Mbps |
ID code (dec.) | 220 | ID code (hex) | DC |
Length code (hex) | 0C | Length code (dec) | 12 |
Process data channel | 192 bit | Input address area | 24 Byte |
Output address area | 24 Byte | Register length | 28 Byte |
Required parameter data | 29 Byte | Required configuration data | 5 Byte |
Product type | I/O component | Type | modular
Inline |
Supply voltage | 7.5 V DC (via voltage jumper) | Current draw | typ. 130 mA |
Connection name | Inline connector | Connection method | Spring-cage connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² | Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 | Stripping length | 8 mm |
Connection method | Spring-cage connection | Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² | Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm | Ambient temperature (operation) | -25 °C ... 60 °C |
Degree of protection | IP20 | Air pressure (operation) | 80 kPa ... 106 kPa (up to 2000 m above sea level) |
Air pressure (storage/transport) | 80 kPa ... 106 kPa (up to 2000 m above sea level) | Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) | Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) | Mounting type | DIN rail mounting |
Specifications may be subject to change without notice