Product Model

IB IL UTH 4/J-ECO

In Stock
Last updated: 2025/5/1
Phoenix Contact IB IL UTH 4/J-ECO

Selling Points

  • 14 differential inputs for thermocouples to measure temperature accurately.
  • 2Measuring range of -210 °C to +1200 °C for versatile temperature monitoring.
  • 32-conductor technology for efficient sensor connection.
  • 4Diagnostic information in the process data word for real-time monitoring.
  • 5IP20 protection ensures safe operation in control cabinets.
Product Details
IB IL UTH 4/J-ECO
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
12.2 mm
Height
119.8 mm
Depth
71.5 mm
Note on application
Only for industrial use
Number of interfaces
2
Connection method
Inline data jumper
Transmission speed
500 kbps
ID code (dec.)
126
ID code (hex)
7E
Length code (hex)
04
Length code (dec)
04
Process data channel
64 bit
Input address area
8 Byte
Output address area
0 Byte
Register length
64 bit
Required parameter data
1 Byte
Required configuration data
4 Byte
Input name
Analog UTH inputs
Description of the input
Differential inputs
Number of inputs
4 (Type J)
Connection method
Inline connector
Connection technology
2-conductor
Note regarding the connection technology
shielded
A/D conversion time
typ. 120 ms
A/D converter resolution
24 bit
Sensor types that can be used (TC)
J
Measuring principle
Sigma/Delta process
Measured value representation
16 bits (15 bits + sign bit)
Process data update
< 10 ms
Protective circuit
Transient protection of inputs
Product type
I/O component
Product family
Inline
Type
modular
Scope of delivery
including Inline connector
Diagnostics messages
Failure of the internal I/O supply I/O error message sent to the bus coupler Checksum error I/O error message sent to the bus coupler
Article revision
02
Maximum power dissipation for nominal condition
1.35 W
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 55 mA typ. 38 mA
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 39 mA typ. 32 mA
Test voltage: Bus logic (local bus, communications power)
500 V AC, 50 Hz, 1 min
Test voltage: Analog I/O
500 V AC, 50 Hz, 1 min
Test voltage: Functional ground
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
0 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice