Product Model
MCR-C-U-U-DC

Selling Points
- 13-way electrical isolation for secure signal processing.
- 2Fixed input and output settings for consistent signal conditioning.
- 3Robust EMC compliance ensuring reliable operation in various environments.
- 4Compact design with dimensions of 12.5 mm x 99 mm x 114.5 mm.
- 5CE-compliant with eCl@ss classifications for international standards.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | Signal conditioner | No. of channels | 1 |
Article revision | 12 | Electrical isolation between input and output | yes |
Limit frequency (3 dB) | 30 Hz | Maximum power dissipation for nominal condition | 450 mW |
Test voltage, input/output/supply | 1.5 kV AC (50 Hz, 60 s) | Protective circuit | Transient protection |
Step response (10-90%) | 11 ms | Maximum temperature coefficient | < 0.015 %/K |
Maximum transmission error | ≤ 0.2 % (of final value) | Transmission error, typical | < 0.1 % (of final value) |
Supply voltage range | 20 V DC ... 30 V DC | Typical current consumption | < 15 mA (without load) |
Description of the input | Voltage input | Number of inputs | 1 |
Configurable/programmable | no | Voltage input signal | 0 V ... 10 V
-10 V ... 10 V |
Max. voltage input signal | 30 V | Input resistance of voltage input | 100 kΩ |
Number of outputs | 1 | Configurable/programmable | no |
Voltage output signal | 0 V ... 10 V
-10 V ... 10 V | Max. voltage output signal | 15 V |
Load/output load voltage output | ≥ 10 kΩ | Linear transmission range (in reference to the output range end value) | -110 % ... 110 % (Bipolar signals) |
Connection method | Pluggable screw connection | Stripping length | 8 mm |
Screw thread | M3 | Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² | Conductor cross section AWG | 24 ... 14 |
Limit frequency (3 dB) | 30 Hz | Width | 12.5 mm |
Height | 99 mm | Depth | 114.5 mm |
Color | green (RAL 6021) | Housing material | Polyamide PA non-reinforced |
Ambient temperature (operation) | -25 °C ... 60 °C | Certificate | CE-compliant |
Mounting type | DIN rail mounting | Mounting position | any |
Specifications may be subject to change without notice