Product Model
MCR-FL-TS-LP-I-EX

Selling Points
- 1Configure the transducer using software for precise temperature measurements.
- 2Supports HART protocol for seamless integration with various systems.
- 3Meets Ex ia IIC standards for safe operation in hazardous environments.
- 4Operates on a loop power supply, reducing the need for external power sources.
- 5Offers a step response of < 2 seconds and a transmission error of ±20 µV for accurate readings.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | Temperature transmitter | Application | Temperature |
Configuration | With HART protocol | Article revision | 07 |
Switch-on delay | 4 s | Line monitoring | NE 43 |
Maximum power dissipation for nominal condition | 105 mW | Test voltage input/output | 2 kV AC (50 Hz, 60 s) |
Step response (10-90%) | < 2 s | Transmission error voltage sensor | ±20 µV (-10 mV ... 100 mV) |
Transmission error thermocouples | typ. 0.5 K (K, J, T, E, L, U), 1.0 K (N, C, D), 2.0 K (S, B, R) | Transmission error resistance-type sensor | ±0.1 Ω (10 ... 400 Ω), ±1.5 Ω (10 ... 2000 Ω) |
Transmission error resistance thermometer | 0.2 K (Pt 100, Ni 100), 0.5 K (Pt 500, Ni 500), 0.3 K (Pt 1000, Ni 1000) | Designation | Loop-powered |
Supply voltage range | 12 V DC ... 30 V DC | Max. current consumption | < 3.5 mA |
Number of inputs | 1 | Input signal | Temperature |
Configurable/programmable | Yes, programmable | Sensor types (RTD) that can be used | Pt, Ni (100, 500, 1000); min. measurement range 10 K |
Sensor types that can be used (TC) | B, C, D, E, J, K, L, N, R, S, T, U; min. measurement range 50 K/500 K | Sensor type: | -200 °C ... 850 °C (freely adjustable)
-200 °C ... 250 °C (freely adjustable)
-200 °C ... 250 °C (freely adjustable)
-60 °C ... 180 °C (freely adjustable)
-60 °C ... 150 °C (freely adjustable)
-60 °C ... 150 °C (freely adjustable)
0 °C ... 1820 °C (freely adjustable)
0 °C ... 2320 °C (freely adjustable)
0 °C ... 2495 °C (freely adjustable)
-270 °C ... 1000 °C (freely adjustable)
-210 °C ... 1200 °C (freely adjustable)
-270 °C ... 1372 °C (freely adjustable)
-200 °C ... 900 °C (freely adjustable)
-270 °C ... 1300 °C (freely adjustable)
-50 °C ... 1760 °C (freely adjustable)
-50 °C ... 1760 °C (freely adjustable)
-270 °C ... 400 °C (freely adjustable)
-200 °C ... 600 °C (freely adjustable) |
Connection technology | 2-, 3-, 4-conductor | Linear resistance measuring range | 10 Ω ... 400 Ω (min. measurement range 10 Ω)
10 Ω ... 2000 Ω (min. measurement range 100 Ω) |
Linear mV signal range | -10 mV ... 100 mV (min. measurement range 5 mV) | Configurable/programmable | no |
Output description | Current output | Number of outputs | 1 |
Configurable/programmable | Yes | Current output signal | 4 mA ... 20 mA
20 mA ... 4 mA |
Max. current output signal | ≤ 23 mA | Output current with short-circuit | ≤ 3.6 mA or ≥ 21 mA (adjustable, not for thermocouples) |
Output current with wire break | ≤ 3.6 mA or ≥ 21 mA (adjustable) | Output current range with overrange/underrange | 3.8 mA ... 20.5 mA |
Load/output load current output | ≤ 520 Ω (At U | Connection method | Screw connection |
Stripping length | 8 mm | Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² | Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 | Tightening torque | 0.5 Nm ... 0.6 Nm |
Max. voltage U | 30 V | Max. current I | 100 mA |
Max. power P | 750 mW | Max. output voltage U | 5 V DC |
Max. output current I | 5.9 mA | Max. output power P | 7.2 mW |
Max. ambient temperature | T4 = 85 °C, T5 = 70 °C, T6 = 55 °C | Safety-related maximum voltage U | 250 V |
IIA: Max. external inductivity L | 100 mH / 10 µF | IIB: Max. external inductivity L | 100 mH / 10 µF |
IIC: Max. external inductivity L | 100 mH / 2 µF | Width | 12.5 mm |
Height | 99 mm | Depth | 114.5 mm |
Color | green (RAL 6021) | Flammability rating according to UL 94 | V0 |
Housing material | Polyamide PA non-reinforced | Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C ... 55 °C | Certificate | CE-compliant |
Identification | II 2(1) G Ex ia IIC T6 | Identification | cULus |
Identification | 2 | Standards/regulations | NAMUR recommendation NE 21 |
Mounting type | DIN rail mounting | Mounting position | any |
Specifications may be subject to change without notice