Product Model

QUINT-DC-UPS/24DC/10

In Stock
Last updated: 2025/5/4
Phoenix Contact QUINT-DC-UPS/24DC/10

Selling Points

  • 1Designed for easy integration into industrial networks.
  • 2Provides up to 10 amps of power during outages.
  • 3Operates between 22.5 V DC and 30 V DC.
  • 4Works from 0°C to 50°C.
  • 5Includes yellow LED for battery charge and status indication.
Product Details
QUINT-DC-UPS/24DC/10
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Input voltage
24 V DC
Input voltage range
22.5 V DC ... 30 V DC
Wide-range input
no
Input voltage range DC
22.5 V DC ... 30 V DC
Voltage type of supply voltage
DC
Buffer period
1.5 min (10 A) 20 min (2 A)
Current consumption
approx. 0.1 A 0.5 A (charging process) 10.5 A (max.)
Fixed backup threshold
< 22 V DC
Variable connect threshold
(U
Input fuse
15 A (slow-blow, internal)
Efficiency
> 91 %
Nominal output voltage
24 V DC (Normal operation: U
Nominal output current (I
10 A
Bridging time
2 min
Short-circuit-proof
yes
Output power
240 W
Power dissipation
20 W 8 W
Connection in parallel
no
Connection in series
yes
Nominal output voltage
24 V DC
Nominal output current (I
10 A
Nominal output voltage
24 V DC
Nominal output current (I
10 A
Output description
Power OK
Output description
Alarm
Maximum switching voltage
≤ 30 V AC/DC
Continuous load current
≤ 1 A
Output description
Battery Charge
Maximum switching voltage
≤ 30 V AC/DC
Continuous load current
≤ 1 A
Output description
Battery Mode
Maximum switching voltage
≤ 30 V AC/DC
Continuous load current
≤ 1 A
Nominal capacity
1.3 Ah
Battery module service life
6 Years (20 °C)
Latest startup date (battery only)
9 Months (20 °C ... 30 °C) 6 Months (30 °C ... 40 °C)
Memory medium
internal, battery 1.3 Ah
Network management
Yes
Connection method
Pluggable screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
7 mm
Screw thread
M3
Connection method
Pluggable screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
7 mm
Screw thread
M3
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Screw thread
M3
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Types of signaling
LED
Operating voltage display
Green LED
Status display
LED "Power OK" green
Note on status display
Power OK: LED permanently lit
Status display
LED (red)
Note on status display
Alarm: LED permanently lit
Status display
LED flashing yellow
Note on status display
Battery charge: LED flashing
Status display
LED (yellow)
Note on status display
Battery mode: LED permanently lit
Insulation voltage input/output
2 kV (routine test) 4 kV (type test)
Product type
DC UPS
Disposal
Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations.
MTBF (IEC 61709, SN 29500)
> 500000 h
Article revision
05
Protection class
II (in closed control cabinet)
Width
100 mm
Height
130 mm
Depth
125 mm
Installation distance right/left
5 mm / 5 mm
Installation distance top/bottom
50 mm / 50 mm
Mounting type
DIN rail mounting
Assembly note
alignable: horizontally 0 mm, vertically 50 mm
Mounting position
horizontal DIN rail NS 35, EN 60715
Housing material
Metal
Type of housing
AluNox (AlMg1)
Degree of protection
IP20
Ambient temperature (operation)
0 °C ... 50 °C
Ambient temperature (storage/transport)
0 °C ... 40 °C
Max. permissible relative humidity (operation)
95 % (at 25 °C, non-condensing)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV) EN 61558-2-17
Standard - Safe isolation
DIN VDE 0100-410
Standard - Safety of transformers
EN 61558-2-17
Shipbuilding approval
DNV GL (EMC A), ABS
UL approvals
UL/C-UL listed UL 508 UL/C-UL Recognized UL 60950-1 UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D
SIL in accordance with IEC 61508
0
Performance level according to ISO 13849
without
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Noise immunity
EN 61000-6-2:2005
Noise emission
EN 55011 (EN 55022)

Specifications may be subject to change without notice