Phoenix Contact UK 16 N-PE/N

Selling Points

  • 1High current capacity up to 76 A.
  • 2Robust design with a nominal cross section of 16 mm².
  • 3Compliant with Ex e area standards (IEC/EN 60079).
  • 4Rated for 800 V nominal voltage.
  • 5Insulation material group I, ensuring high reliability.
Product Details
UK 16 N-PE/N
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Ground terminal block
Number of connections
2
Number of rows
1
Article revision
08
Overvoltage category
III
Degree of pollution
3
Rated surge voltage
8 kV
Maximum power dissipation for nominal condition
0 W
PEN function
yes
Grounding foot
Yes
Number of connections per level
2
Screw thread
M4
Note
Please observe the current carrying capacity of the DIN rails.
Tightening torque
1.5 ... 1.8 Nm
Stripping length
11 mm
Internal cylindrical gage
B7
Connection in acc. with standard
IEC / EN 
Conductor cross section rigid
2.5 mm² ... 25 mm²
Cross section AWG
12 ... 4 (converted acc. to IEC)
Conductor cross section flexible
4 mm² ... 16 mm²
Conductor cross section, flexible [AWG]
10 ... 6 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)
1.5 mm² ... 16 mm²
Flexible conductor cross section (ferrule with plastic sleeve)
1.5 mm² ... 16 mm²
Nominal current
101 A
Maximum load current
101 A (with 25 mm² conductor cross section)
Nominal voltage
690 V
Width
24.4 mm
Height
42.5 mm
Depth on NS 32
59 mm
Depth on NS 35/7,5
54 mm
Depth on NS 35/15
61.5 mm
Color
multicolored green-yellow blue (RAL 5015)
Flammability rating according to UL 94
V0
Insulating material group
I
Insulating material
PA
Static insulating material application in cold
-60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130 °C
Relative insulation material temperature index (Elec., UL 746 B)
130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354)
28 MJ/kg
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Terminal block mounting
1.5 Nm ... 1.8 Nm (PE foot with mounting screw, M4)
Open side panel
No
Ambient temperature (operation)
-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Permissible humidity (storage/transport)
30 % ... 70 %
Connection in acc. with standard
IEC / EN 
Mounting type
NS 35/7,5 NS 35/15 NS 32
Terminal block mounting
1.5 Nm ... 1.8 Nm (PE foot with mounting screw, M4)

Specifications may be subject to change without notice