Phoenix Contact UT 16 BN

Selling Points

  • 1High Current Capacity: Handles up to 76A with a rated voltage of 1kV.
  • 2Durable Construction: Made with polyamide insulator and M5 screw connection for reliability.
  • 3Versatile Mounting: Compatible with DIN Rail mounting (NS 35/7,5, NS 35/15).
  • 4Flexible Wiring Options: Accepts wire sizes from 16 to 4 AWG.
  • 5Easy Installation: Includes reducing bridges for connecting terminal blocks with different technologies.
Product Details
UT 16 BN
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Feed-through terminal block
Area of application
Railway industry Machine building Plant engineering Process industry
Number of connections
2
Number of rows
1
Potentials
1
Article revision
03
Overvoltage category
III
Degree of pollution
3
Rated surge voltage
8 kV
Maximum power dissipation for nominal condition
2.43 W
Number of connections per level
2
Nominal cross section
16 mm²
Screw thread
M5
Tightening torque
2.5 ... 3 Nm
Stripping length
14 mm
Internal cylindrical gage
A7
Connection in acc. with standard
IEC 60947-7-1
Conductor cross section rigid
1.5 mm² ... 25 mm²
Cross section AWG
14 ... 4 (converted acc. to IEC)
Conductor cross section flexible
1.5 mm² ... 25 mm²
Conductor cross section, flexible [AWG]
14 ... 4 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)
1 mm² ... 16 mm²
Flexible conductor cross section (ferrule with plastic sleeve)
1 mm² ... 16 mm²
2 conductors with same cross section, solid
1 mm² ... 6 mm²
2 conductors with same cross section, flexible
1 mm² ... 6 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
1 mm² ... 6 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve
0.75 mm² ... 10 mm²
Nominal current
76 A
Maximum load current
101 A (with 25 mm² conductor cross section)
Nominal voltage
1000 V
Note
Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area.
Nominal cross section
16 mm²
Width
12.2 mm
End cover width
2.2 mm
Height
55.5 mm
Depth
54.4 mm
Depth on NS 35/7,5
55 mm
Depth on NS 35/15
62.5 mm
Color
brown (RAL 8028)
Flammability rating according to UL 94
V0
Insulating material group
I
Insulating material
PA
Open side panel
Yes
Ambient temperature (operation)
-60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, no longer than 24 h, -60°C to +70°C)
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Permissible humidity (operation)
20 % ... 90 %
Permissible humidity (storage/transport)
30 % ... 70 %
Connection in acc. with standard
IEC 60947-7-1
Mounting type
NS 35/7,5 NS 35/15

Specifications may be subject to change without notice