Rockwell Automation 150-C108NCD

Selling Points

  • 11. Advanced Control Modes: The 150-C108NCD offers four starting modes—soft start, soft stop, current limiting, and kick start—to ensure safe and efficient motor operation.;
  • 22. Integrated Protection: Equipped with run bypass activation and overload/fault detection, this controller provides reliable performance and minimizes downtime.;
  • 33. Delta Compatibility: Compatible with Delta configurations, making it versatile for various industrial applications.;
  • 44. Customizable Start Times: Allows customizable start times ranging from 2 to 30 seconds, enhancing control over motor operations.;
  • 55. Compact Design: Features a compact, user-friendly design that fits seamlessly into industrial settings, reducing space requirements while maintaining high performance.
Product Details
150-C108NCD
Rockwell Automation

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Dimension Unit
CM
Weight Unit
KG
Stock Status
STOCKED
Dimension Length
62.23
Dimension Width
36.195
Lead Time
21
Dimension Height
34.925
Quick Turnaround
false
Preferred Availability
false
Repairable
REPAIRABLE
Enclosure
Open type
Power pole holes
One M10 x 1.5 diam hole per power pole for load Power Terminals
Number of poles
Equipment is designed for 3-phase only for power circuit
Mounting hole size
7.5 mm
Pollution degree
2
Altitude
2000 m
EMC immunity levels
Surge transient: per EN/IEC 60947-4-2 per IEC
EMC emission levels
Radiated emission: Class A per IEC
Operating temperature
Open: -5 to 50 °C (23 to 122 °F)
Humidity
5...95% noncondensing
Rated surrounding temperature range without derating
-5 °C
Storage and transportation temperature
-25 °C
Steady state heat dissipation
62 W
Selectable soft stop
Off, 100%, 200%, or 300% of the start time setting when wired
Selectable initial torque
15%, 25%, 35%, and 65% of locked rotor torque
Selectable kick start - 450% FLA
0, 0.5, 1.0, or 1.5 s
Function
Single direction
Internal bypass
Yes
Tightening torque
0.45...0.9 Nm (4.0...8.0 in-lb) for control terminals
Break
TB-97, -98 (OVLD/Fault): 72VA for auxiliary contacts
Make
TB-97, -98 (OVLD/Fault): 432VA for auxiliary contacts
Vibration
Opsal: 1.0 G peak, 0.15 mm (0.006 in) displacement
Cable size
0.2...2.5 mm2 (24...14 AWG) for control terminals
Height
443.7 mm (17.47 in)
Depth
205.2 mm (8.08 in)
Width
196.4 mm (7.74 in)
Shock
Opsal: 15 G
Weight
16.825
Degree of protection (IP)
IP2X
Input ON-state current (IN1, IN2)
9.8mA @ 120V AC/19.6mA @ 240V AC for control circuit, 7.3mA @ 24V AC/DC for control circuit
Input ON-state voltage, during start (IN1, IN2)
85V AC @ 19.2V DC/19.2V AC minimum for control circuit
Selectable current limit
150%, 250%, 350%, and 450% of full load current
Input OFF-state voltage (IN1, IN2), max
40V AC @ 17V DC/12V AC for control circuit
Selectable start times
2, 5, 10, 15, 20, 25, or 30 s
Selectable overload trip class
Trip Class 10, 15, or 20
Short circuit protection device performance (SCPD) type
Type 1
Integrated motor overload protection
Yes
Standard available fault current, max
10 kA @ maximum standard fuse 600 A for delta device opsal current rating
Standard controller feature
Soft stop
Rated operational current, max
TB-97, -98 (OVLD/Fault): 0.6A @ 120V AC and 0.3A @ 240V AC for auxiliary contacts
Utilization category
TB-23, -24 (normal/up-to-speed), TB-33, -34 (normal/up-to-speed): C300/R150 per UL/CSA/NEMA for Side mount auxiliary contacts
Type of contacts
TB-97, -98 (OVLD/Fault): Normally Open (N.O.) for auxiliary contacts
Type of control circuit
TB-97, -98 (OVLD/Fault): Electromagnetic relay for auxiliary contacts
Conventional thermal current (Ith)
TB-97, -98 (OVLD/Fault): 1 A for auxiliary contacts
Type of current
TB-97, -98 (OVLD/Fault): AC/DC for auxiliary contacts
High capacity available fault current, max
70kA @ 600V, maximum current 400 A time delay Class J or Class L fuse for inside delta connected motors
Number of contacts
TB-97, -98 (OVLD/Fault): 1 for auxiliary contacts
Short-circuit protection device list
Non-time delay Thermal magnetic circuit breaker High capacity time delay class CC/J/L
Input OFF-state current
<10 mA, <12 mA @ input off-state voltage (IN1, IN2) for control circuit
Rated control power during start with fan
200mA @ 120V AC/120mA @ 240V AC, 600mA @ 24V AC/DC
Rated operational voltage
250V AC/30V DC per UL/CSA/NEMA for Side mount auxiliary contacts
Insulation voltage
Rated 600V AC per UL/CSA/NEMA for power circuit
Delta connected motor current
47...187A @ 500/575V AC, 3-phase
Dielectric withstand
2500V AC per IEC for power circuit
Rated impulse voltage
6 kV for power circuit
Overvoltage category
III per IEC for side mount auxiliary contacts
Operating frequency
50/60 Hz per UL/CSA/NEMA for power circuit
Repetitive peak voltage
1600V per UL/CSA/NEMA for power circuit
DV/DT protection
1000V/μs for power circuit
Controller type
SMC-3
Overload current
27 A
Fan power rating
20 VA
Rated control supply voltage at AC 60 Hz
100
Rated control supply voltage at AC 50 Hz
100
Rated operating voltage Ue
200
Voltage type for actuating
AC/DC
With display
No
Product Family
SMC-3

Specifications may be subject to change without notice