Rockwell Automation 150-C85NCD

Selling Points

  • 11. High Performance: The 150-C85NCD is designed to handle high current loads of up to 85A at 600V, ensuring reliable operation in demanding industrial environments.;
  • 22. Versatile Power Supply: Compatible with both 100-240V AC, 50/60Hz, this controller can be easily integrated into various industrial settings without requiring additional power supply adjustments.;
  • 33. Efficient Operation: Optimized for efficient motor operation, the 150-C85NCD reduces energy consumption and extends the lifespan of your motors, making it a cost-effective solution.;
  • 44. Industrial Grade: Built with high-quality components, this controller is engineered to withstand harsh industrial conditions, ensuring consistent performance over time.;
  • 55. Easy Integration: Designed for seamless integration with Allen Bradley systems, the 150-C85NCD simplifies your automation setup, reducing installation time and complexity.
Product Details
150-C85NCD
Rockwell Automation

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Dimension Unit
CM
Weight Unit
KG
Weight
3.334
Stock Status
NON_STOCKED
Dimension Length
30.201
Dimension Width
21.412
Lead Time
5
Dimension Height
14.707
Quick Turnaround
false
Preferred Availability
false
Repairable
NOT_REPAIRABLE
Enclosure
Open type
Number of poles
Equipment is designed for 3-phase only for power circuit
Pollution degree
2
Altitude
2000 m
EMC immunity levels
Surge transient: per EN/IEC 60947-4-2 per IEC
EMC emission levels
Radiated emission: Class A per IEC
Operating temperature
Open: -5 to 50 °C (23 to 122 °F)
Humidity
5...95% noncondensing
Rated surrounding temperature range without derating
-5 °C
Storage and transportation temperature
-25 °C
Selectable soft stop
Off, 100%, 200%, or 300% of the start time setting when wired
Selectable initial torque
15%, 25%, 35%, and 65% of locked rotor torque
Selectable kick start - 450% FLA
0, 0.5, 1.0, or 1.5 s
Function
Single direction
Internal bypass
Yes
Break
TB-97, -98 (OVLD/Fault): 72VA for auxiliary contacts
Make
TB-97, -98 (OVLD/Fault): 432VA for auxiliary contacts
Vibration
Opsal: 1.0 G peak, 0.15 mm (0.006 in) displacement
Shock
Opsal: 15 G
Degree of protection (IP)
IP2X
Input ON-state current (IN1, IN2)
9.8mA @ 120V AC/19.6mA @ 240V AC for control circuit, 7.3mA @ 24V AC/DC for control circuit
Input ON-state voltage, during start (IN1, IN2)
85V AC @ 19.2V DC/19.2V AC minimum for control circuit
Selectable current limit
150%, 250%, 350%, and 450% of full load current
Input OFF-state voltage (IN1, IN2), max
40V AC @ 17V DC/12V AC for control circuit
Selectable start times
2, 5, 10, 15, 20, 25, or 30 s
Selectable overload trip class
Trip Class 10, 15, or 20
Short circuit protection device performance (SCPD) type
Type 1
Integrated motor overload protection
Yes
Standard controller feature
Soft stop
Rated operational current, max
TB-97, -98 (OVLD/Fault): 0.6A @ 120V AC and 0.3A @ 240V AC for auxiliary contacts
Utilization category
TB-23, -24 (normal/up-to-speed), TB-33, -34 (normal/up-to-speed): C300/R150 per UL/CSA/NEMA for Side mount auxiliary contacts
Type of contacts
TB-97, -98 (OVLD/Fault): Normally Open (N.O.) for auxiliary contacts
Type of control circuit
TB-97, -98 (OVLD/Fault): Electromagnetic relay for auxiliary contacts
Conventional thermal current (Ith)
TB-97, -98 (OVLD/Fault): 1 A for auxiliary contacts
Type of current
TB-97, -98 (OVLD/Fault): AC/DC for auxiliary contacts
High capacity available fault current, max
70kA @ 600V, maximum current 300 A time delay Class J or Class L fuse for inside delta connected motors
Number of contacts
TB-97, -98 (OVLD/Fault): 1 for auxiliary contacts
Short-circuit protection device list
Non-time delay Thermal magnetic circuit breaker High capacity time delay class CC/J/L
Input OFF-state current
<10 mA, <12 mA @ input off-state voltage (IN1, IN2) for control circuit
Rated operational voltage
250V AC/30V DC per UL/CSA/NEMA for Side mount auxiliary contacts
Insulation voltage
Rated 600V AC per UL/CSA/NEMA for power circuit
Dielectric withstand
2500V AC per IEC for power circuit
Rated impulse voltage
6 kV for power circuit
Overvoltage category
III per IEC for side mount auxiliary contacts
Operating frequency
50/60 Hz per UL/CSA/NEMA for power circuit
Repetitive peak voltage
1600V per UL/CSA/NEMA for power circuit
DV/DT protection
1000V/μs for power circuit
Controller type
SMC-3
Rated control supply voltage at AC 60 Hz
100
Rated control supply voltage at AC 50 Hz
100
Rated operating voltage Ue
200
Voltage type for actuating
AC/DC
With display
No

Specifications may be subject to change without notice