Rockwell Automation 2080-MOT-HSC

Selling Points

  • 11. Advanced Counter Capabilities: The 2080-MOT-HSC supports high-speed counter operations, making it ideal for applications requiring precise and rapid counting.;
  • 22. Robust Industrial Specifications: Designed to withstand harsh industrial environments, this module meets IEC 60068-2-1, IEC 60068-2-2, and IEC 60068-2-14 standards for operating and non-operating temperatures.;
  • 33. Differential Input Support: Equipped with differential inputs, the module supports two input terminals for each input point, ensuring reliable and accurate data collection.;
  • 44. High ESD Immunity: The module boasts high ESD immunity, with 6 kV contact discharges and 8 kV air discharges, ensuring reliable operation in environments with high electromagnetic interference.;
  • 55. Compact Design: With dimensions of 31.5 mm in width, 62 mm in height, and 20 mm in depth, the 2080-MOT-HSC is compact and easy to integrate into your existing systems.
Product Details
2080-MOT-HSC
Rockwell Automation

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Dimension Unit
CM
Weight Unit
G
Weight
52.163
Stock Status
STOCKED
Dimension Length
10.389
Dimension Width
6.502
Lead Time
5
Dimension Height
5.207
Quick Turnaround
false
Preferred Availability
false
Repairable
NOT_REPAIRABLE
ON-state voltage range
2.6...30V DC
Off-state leakage current
0.5 mA
Input voltage range
0...30V DC
Input current range
2 mA
Phase separation, min
500 ns
Maximum count
48 bit
Input frequency, max
250 kHz (50% duty)
Input impedance, nom
3580 ?
Pulse width, min
2 μs
Number of inputs
1 Quadrature (ABZ) differential input
On-state current, min
2 mA
Off-state voltage, max
1.0V DC
Output voltage range
5...30V DC
Enclosure type rating
Meets IP20
Number of outputs
16 (1 physical output, 15 virtual)
Output on-state current
0.5 A
Reverse polarity protection
None
On-state voltage drop, max
0.5V DC
Radiated RF immunity
IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz,
Nonoperating temperature
-40...85 °C (-40...185 °F), IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
Surge transient immunity
IEC 61000-4-5: ±2 kV line-earth(CM) on shielded ports
Operating temperature
-20...65 °C (-4...149 °F): IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, operating dry heat), IEC 60068-2-14 (Test Nb, operating thermal shock)
EFT/B immunity
IEC 61000-4-4: ±2kV @ 5kHz on signal ports
Conducted RF immunity
IEC 61000-4-6, 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Relative humidity
IEC 60068-2-30 (Test Db, unpackaged dA heat), 5...95% noncondensing
ESD immunity
IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges
Emissions
CISPR 11 (IEC 61000-6-4): Class A
North American temperature code
T4
Surrounding air temperature, max
65 °C
Terminal screw torque
0.22...0.25 Nm (1.95...2.21 in-lb) (using a 2.5 mm (0.10 in.) flat-blade screwdriver)
Vibration
IEC 60068-2-6 (Test Fc, operating), 2 G @ 10...500 Hz
Shock
IEC 60068-2-27 (Test Ea, unpackaged shock): 25 g, nonoperating, 35 g (Panel Mount) nonoperating
Depth
20 mm
Height
62 mm
Width
31.5 mm
Bus current draw
60mA @ 3.3V DC
Short-circuit protection, outputs available
No
Redundancy
No
Isolation voltage
Input module: 50V (continuous), Basic Insulation Type, Inputs/Outputs to Backplane. Type tested for 60s @ 720V DC, Inputs/Outputs to Backplane
Wire size
Solid: 0.14 mm2 AWG)...1.5 mm2 AWG) @ Rated @ 90 °C (194 °F) insulation maximum, Stranded: 0.14 mm2 AWG)...1.0 mm2 AWG) @ Rated @ 90 °C (194 °F) insulation maximum
Wiring category
2 - on signal ports
Type of electric connection
Screw connection
Type of digital output
Other
Type of output voltage
DC
Type of voltage (input voltage)
DC
Digital outputs configurable
Yes
Digital inputs configurable
Yes
Suitable for safety functions
Yes
Time delay at signal exchange
2 ms
I/O Status Indication
LED
I/O Isolation
None

Specifications may be subject to change without notice